iDrive2 inverters
Function
Name
code
Output upper
P09.09
limit of PID
Output lower
P09.10
limit of PID
Feedback
offline
P09.11
detection
value
Feedback
offline
P09.12
detection
time
PID
P09.13
adjustment
selection
Detailed instruction of parameters
Setting range:0.0~100.0%
These parameters are used to set the upper and lower
limit of the PID adjustor output.
100.0 % corresponds to Max. Frequency
Setting range of P09.09: P09.10~100.0%
Setting range of P09.10: -100.0%~P09.09
Set the PID feedback offline detection value, when the
detection value is smaller than or equal to the feedback
offline detection value, and the lasting time exceeds the
set value in P09.12, the inverter will report "PID
feedback offline fault" and the keypad will display PIDE.
Setting range of P09.11: 0.0~100.0%
Setting range of P09.12: 0.0~3600.0s
0x00~0x11
LED ones:
0: Keep on integral adjustment when the frequency
achieves the upper and low limit; the integration shows
the change between the reference and the feedback
unless it reaches the internal integral limit. When the
trend between the reference and the feedback changes,
it needs more time to offset the impact of continuous
working and the integration will change with the trend.
1: Stop integral adjustment when the frequency reaches
the upper and low limit. If the integration keeps stable,
and the trend between the reference and the feedback
changes, the integration will change with the trend
56
Function Parameters
Default
Modify
value
100.0%
0.0%
0.0%
1.0s
0x00