IMO iDrive2 XKL Instruction Manual page 60

General application inverter
Table of Contents

Advertisement

iDrive2 inverters
Function
Name
code
test level
Overload
pre-alarm
P11.10
detection
time
Detection
level of the
P11.11
underload
pre-alarm
Detection
time of the
P11.12
underload
pre-alarm
Detailed instruction of parameters
Setting range of P11.08:
Enable and define the overload pre-alarm of the inverter
or the motor.
Setting range: 0x000~0x131
LED ones:
0:Overload pre-alarm of the motor, comply with the rated
current of the motor
1:Overload pre-alarm of the inverter, comply with the
rated current of the inverter
LED tens:
0:The inverter continues to work after underload
pre-alarm
1:The inverter continues to work after underload
pre-alarm and the inverter stops to run after overload
fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops to run after underload
fault
3. The inverter stops when overloading or underloading.
LED hundreds :
0:Detection all the time
1:Detection in constant running
Setting range of P11.09: P11.11~200%
Setting range of P11.10: 0.1~60.0s
If the inverter current or the output current is lower than
P11.11, and exceeds time set in P11.12, the inverter will
output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~60.0s
60
Function Parameters
Default
Modify
value
1.0s
50%
1.0s