iDrive2 inverters
Function
Name
code
Overvoltage
P11.03
speed loss
protection
Overvoltage
speed loss
P11.04
voltage
protection
Current limit
P11.05
action
selection
Automatic
P11.06
current limit
level
The
decreasing
P11.07
ratio during
current limit
Overload
pre-alarm of
P11.08
the motor or
the inverter
Overload
P11.09
pre-alarm
Detailed instruction of parameters
2. Prohibition of input phase protection can enable this
function.
0:Disabled
1:Enabled
120~150%(standard bus voltage)(400V)
120~150%(standard bus voltage)(230V)
During the running of the inverter, this function will detect
the output current and compare it with the limit level
defined in P11.06. If it exceeds the level, the inverter will
run at stable frequency in ACC running, or the inverter
will derate to run during the constant running. If it
exceeds the level continuously, the output frequency will
keep on decreasing to the lower limit. If the output
current is detected to be lower than the limit level, the
inverter will accelerate to run.
Setting range of P11.05:
0:current limit invalid
1:current limit valid
Setting range of P11.06:50.0~200.0%
Setting range of P11.07:0.00~50.00Hz/s
The output current of the inverter or the motor is above
P11.09 and the lasting time is beyond P11.10, overload
pre-alarm will be output.
59
Function Parameters
Default
Modify
value
1
140%
120%
1
160.0%
10.00Hz/
s
0x000
150%

Hide quick links: