Configuring the ACU+ Identification of Converter Modules

When converters are all installed prior to applying power and starting the system, the
order in which the ACU+ identifies the converters is by serial number (lowest serial
number is Conv 1, next lowest is Conv 2, etc.).
If you prefer the ACU+ to identify the converters by position in the system, perform the
following procedure.
Procedure
Chapter 5. Installing the Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NPBA
5) If you wish to change the Rectifier IDs, navigate to and select "Rectifier ID".
Press ENT. Use the up or down keys to change the ACU+ identification number
for the flashing rectifier. Press ENT.
6) If you wish to change the Rectifier Phase Assignment, navigate to and select
"Rect Phase". Press ENT. Use the up or down keys to change the phase
connected to the flashing rectifier. Press ENT.
Note: The new ID and/or phase assignment will not take effect until this entire
procedure is completed and the new ID's have been confirmed.
7) Press ESC to return to rectifier menu screen.
8) Navigate to and select the next rectifier.
9) Repeat steps 4) through 8) for each of the remaining rectifiers in the system.
10) When you have finished selecting identification numbers for all rectifiers,
repeatedly press ESC to return to the Main Menu.
11) Navigate to and select "Manual" (ENT) / "Rectifier" (ENT) / "All Rect Ctrl"
(ENT).
12) Navigate to "Confirm ID/PH". Press ENT. "Yes" highlights.
13) Press ENT to select the operation. Press ENT again to confirm.
Note: Check you numbering to be sure it is correct. If there where conflicts in your
numbering, rectifiers with conflicts will be assigned the next available
sequential number.
14) Return to the Main screen by repeatedly pressing ESC (escape).
1) With the Main screen displayed, press ENT to go to the Main Menu. Navigate to
and select "Settings" (ENT).
2) If a password screen opens, a password must be entered to allow the User to
make adjustments. If a password was previously entered and has not yet timed
out, skip this step and proceed to step 3). Otherwise, to enter a password, with
the cursor at the User Name field (default is "Admin"), press the down arrow key
to move cursor down to the password line. Press ENT. "0" is highlighted. Press
the up arrow key once to change the "0" to"1" (default password is "1"), then
press ENT twice. (Note: If you have been assigned a unique User Name and
password, follow this procedure to enter these.)
3) With the Settings menu screen displayed, navigate to and select "Converter"
(ENT).
4) Navigate to "Conv #" (# is used here to represent the converter identification
number). Press ENT. The converter # menu screen is displayed, and the green
LED on one converter starts flashing. This is the converter currently identified by
the ACU+ as converter #. (If this is not the converter you want, press ESC to
return to converter menu screen and select a different converter.)
IM581127000
Issue AB, March 22, 2012
Page 99