Emerson NetSure 710NPBA Installation Instructions Manual page 92

+24v dc power system
Table of Contents

Advertisement

IM581127000
Issue AB, March 22, 2012
1. Remove top Rear Access Cover
from distribution cabinet
(note that the complete
rear cover is removed in the
illustration for clarity only).
2. Attach Return Angle Bracket.
3. Attach +24V Angle Bracket.
4. Secure rear cover shield
to distribution cabinet
after wiring.
Plastic Shield
Apply electrical anti-oxidizing
compound to busbar mating surfaces.
Page 84
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Hardware attached
from other side.
Rear View
+24V Angle Bracket
Secure in 2 places
with existing hardware
(in order listed)
1/2-13 x 1-1/4" Bolt,
1/2" Belleville Lockwasher,
1/2" Flat Washer.
Torque to 200 in-lbs.
Return Angle Bracket
Secure 2 places
with (in order listed)
3/8-16 x 1-1/4" Bolt,
3/8" Belleville Lockwasher,
and 3/8" Flat Washer.
Torque to 180 in-lbs.
Figure 4-16
Battery Landing Busbar Kit P/N 550265
Chapter 4. Making Electrical Connections
Installation Instructions
Spec. No. 581127000 (Model 710
(Two Row Cabinet
Shown, Others Similar)
)
NPBA