Emerson NetSure 710NPBA Installation Instructions Manual page 113

+24v dc power system
Table of Contents

Advertisement

Installation Instructions
Spec. No. 581127000 (Model 710
Chapter 5. Installing the Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NPBA
6) With the Settings menu screen displayed, navigate to "Power System" (ENT) /
"General" (ENT) / "24V Over Volt1". Record the displayed voltage setpoint.
7) Press ENT. Use the up or down arrow keys to adjust the "24V Over Volt1" value
to one volt below the system voltage recorded in step 3). Press ENT.
a) Requirement: An audible alarm sounds. The alarm will be silenced in
Requirement c).
b) Requirement: ACU+ "Critical/Major" alarm indicator goes from off to red.
c) Requirement: Press ESC repeatedly to return to the Main screen. ACU+
displays "Alarm".
To see the specific alarm, press ENT to display the Main Menu.
Navigate as follows: "Status" (ENT) / "Active Alarm" (ENT).
The Active Alarm screen lists one critical alarm.
Press ENT. "Power System 24V Over Volt1 Critical" is displayed.
d) Requirement: External "Relay 1 Critical Summary Alarm" and "Relay 3 Over
Voltage 1 Alarm" activate.
8) Without readjusting the "24V Over Volt1" setpoint, press the ESC key repeatedly
to return to the Main Menu. Then navigate as follows: Settings (ENT) / "Power
System" (ENT) / "General" (ENT) / "24V Over Volt2". Record the displayed
voltage setpoint.
9) Press ENT. Use the up or down arrow keys to adjust the "24V Over Volt2" value
to one-half volt below the system voltage recorded in step 3). Press ENT.
a) Requirement: An audible alarm sounds. Alarm will be silenced in
Requirement c).
b) Requirement: ACU+ "Critical/Major" alarm indicator stays red.
c) Requirement: Press ESC repeatedly to return to the Main screen. ACU+
displays "Alarm".
To see the specific alarm, press ENT to display the Main Menu.
Navigate as follows: "Status" (ENT) / "Active Alarm" (ENT).
The Active Alarm screen lists two critical alarms.
Press ENT. "Power System 24V Over Volt2 Critical" is displayed.
Use arrow keys to scroll through the list of alarms.
"Power System 24V Over Volt1 Critical" is displayed.
d) Requirement: External "Relay 1 Critical Summary Alarm" and "Relay 3 Over
Voltage 1 Alarm" remain active.
10) Press ESC repeatedly to return to the Main Menu. Navigate to "Settings" (ENT)
/ "Power System" (ENT) / "General" (ENT) / "24V Over Volt2".
11) Press ENT. Use the up or down arrow keys to adjust the "24V Over Volt2"
setting to the value recorded in step 8). Press ENT.
12) Use the up or down arrow keys to scroll up to "24V Over Volt1".
13) Press ENT. Use the up or down arrow keys to adjust the "24V Over Volt1"
setting to the value recorded in step 6). Press ENT.
a) Requirement: ACU+ "Critical/Major" alarm indicator goes from red to off.
b) Requirement: Press ESC repeatedly to return to the Main screen. ACU+
displays "No Alm".
c) Requirement: All external alarms deactivate.
IM581127000
Issue AB, March 22, 2012
Page 105

Advertisement

Table of Contents
loading

This manual is also suitable for:

581127000

Table of Contents