INSTALLING CIRCUIT BREAKER
ALARM WIRING (BREAKERS W/OUT SHUNTS)
Page 24
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Apply anti-oxidizing compound to busbar mating
surfaces before mounting circuit breakers.
INSTALLING CIRCUIT BREAKER GUARD
ALARM WIRING (BREAKERS WITH SHUNTS)
Figure 2-14 (cont'd on next page)
Installing a GJ/218 Circuit Breaker (1-Pole)
Chapter 2. Installing the System
Spec. No. 581127000 (Model 710
Alarm jumper connector.
Holes to route shunt jumper through (if applicable).
ON
OFF
Installation Instructions
)
NPBA
1/4" Hardened
Flat Washer
1/4" Belleville
Lock Washer
1/4-20 x 3/4" Bolt
(2 places)
Torque to 60 in-lbs.