Emerson NetSure 710NPBA Installation Instructions Manual page 76

+24v dc power system
Table of Contents

Advertisement

IM581127000
Issue AB, March 22, 2012
List AE: +24V Distribution Panel,
(2) TPH Fuse Positions (without Shunts) (without Return Busbar)
For an 800A circuit breaker,
load must not exceed 600A.
List AF: +24V Distribution Panel,
(2) TPH Fuse Positions (with Shunts) (without Return Busbar)
For an 800A circuit breaker,
load must not exceed 600A.
Page 68
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
+24VDC Load
Connections
+24VDC Load
Connections
Chapter 4. Making Electrical Connections
Spec. No. 581127000 (Model 710
LOAD CONNECTIONS
3/8-16 Captive Nuts on 1" Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.88 inches.
Observe proper
polarity when making
load connections.
LOAD CONNECTIONS
3/8-16 Captive Nuts on 1" Centers
(Customer must supply or order additional hardware)
Maximum Lug Width: 1.88 inches.
Observe proper
polarity when making
load connections.
Installation Instructions
NPBA
WARNING!
WARNING!
)