Checking Circuit Breaker/Fuse Alarm Procedure
Checking High 2 Battery Temperature Alarm Procedure
Note: This procedure requires a battery temperature probe and is performed via the
Page 106
Chapter 5. Installing the Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
1) Verify system is operating and no alarms are present.
2) Verify the ACU+ displays the Main screen. If not, press ESC repeatedly to return
to the Main screen.
3) Open the distribution cabinet's front door by turning the latch in the
counterclockwise position.
Note: The following procedure is to be used only with circuit breakers that provide
an alarm indication when manually placed to the OFF (open) position (black
handle). Electrical trip alarm circuit breakers (white handle) cannot be easily
tested in the field.
4) Do one of the following: (1) Remove a good fuse or a dummy fuse from a GMT
fuse position and replace it with a blown fuse, or (2) Remove a good GMT alarm
type fuse from a fuse block containing it and replace it with a blown fuse, or (3)
Place the handle (if black) of a circuit breaker in the OFF (open) position.
a) Requirement: An audible alarm sounds. Alarm will be silenced in
Requirement c).
b) Requirement: ACU+ "Critical/Major" alarm indicator goes from off to red.
c) Requirement: ACU+ displays "Alarm".
To see the specific alarm, press ENT to display the Main Menu.
Navigate as follows: "Status" (ENT) / "Active Alarm" (ENT).
The Active Alarm screen lists one critical alarm.
Press ENT. "DC Fuse Unit Row # FA Critical" is displayed.
d) Requirement: External "Relay 1 Critical Summary Alarm" and "Relay 7
Fuse Alarm" activate.
5) Do one of the following: (1) Replace the blown GMT fuse with the fuse removed,
or (2) Replace the blown GMT alarm type fuse with the fuse removed, or (3)
Place the handle of the circuit breaker in the ON (closed) position.
a) Requirement: ACU+ "Critical/Major" alarm indicator goes from red to off.
b) Requirement: Press ESC repeatedly to return to the Main screen. ACU+
displays "No Alm".
c) Requirement: All external alarms deactivate.
Web Interface.
1) Verify system is operating and no alarms are present.
2) Via the Web Interface, navigate to Device Information / Battery Group / Status
Tab. Record the "IB2 Temp1" temperature reading.
3) Select the Settings tab in the same screen. Record the "IB2 Temp1 High 1"
setpoint.
4) Adjust the "IB2 Temp1 High 1" setpoint to 20 degrees below the temperature
recorded in step 2).
a) Requirement: An "IB2 Temp1 High 1" alarm is displayed.
5) From the same screen, record the "IB2 Temp1 High 2" setpoint.
Installation Instructions
Spec. No. 581127000 (Model 710
)
NPBA