Emerson NetSure 211 C23 User Manual

Emerson NetSure 211 C23 User Manual

Embedded power supply system

Advertisement

NetSure 211 C23 Embedded Power
Supply System
User Manual
Version
V1.0
Revision date September 15, 2009
BOM
31012177
Emerson Network Power provides customers with
technical support. Users may contact the nearest
Emerson local sales office or service center.
Copyright © 2009 by Emerson Network Power
Co., Ltd.
All rights reserved. The contents in this document
are subject to change without notice.
Emerson Network Power Co., Ltd.
Address: No.1 Kefa Rd., Science & Industry Park,
Nanshan District 518057, Shenzhen China
Homepage: www.emersonnetworkpower.com.cn
E-mail: support@emersonnetwork.com.cn

Advertisement

Table of Contents
loading

Summary of Contents for Emerson NetSure 211 C23

  • Page 1 Revision date September 15, 2009 31012177 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice.
  • Page 2: Safety Precautions

    When operating Emerson products, the operation personnel must observe the safety rules in the industry, the general safety points and special safety instructions specified in this book.
  • Page 3 IV. ESD Note The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive components.
  • Page 4 Others I. Safety Note Noti ce Warning When replacing power input fuses of monitoring module and power distribution units, use the same type fuses to meet the safety requirement. II. Sharp object Warning When moving equipment by hand, wear protective gloves to avoid injury by sharp object. III.
  • Page 5: Table Of Contents

    Contents Chapter 1 Overview ................................1 1.1 Model Description ..............................1 1.2 Composition And Configuration ..........................1 1.3 Features ................................2 Chapter 2 Installation Instruction ............................3 2.1 Safety Regulations ..............................3 2.2 Preparation ................................3 2.3 Mechanical Installation ............................4 2.4 Electrical Installation .............................
  • Page 7: Chapter 1 Overview

    Chapter 1 Overview Chapter 1 Overview This chapter introduces model description, composition and configuration, and features of NetSure 211 C23 embedded power supply system (abbreviated as ‘system’ hereinafter). 1.1 Model Description The model description of the system is given in Figure 1-1.
  • Page 8: Features

     The monitoring module is of network design. With an RS232 port, Ethernet, dry contacts and other communication ports provided, flexible networking is enabled to achieve remote monitoring and unattendance.  The system has complete fault protection and fault alarm functions. NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 9: Chapter 2 Installation Instruction

    The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by representatives of both the user and Emerson Network Power Co., Ltd. To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the equipment is correct and complete.
  • Page 10: Mechanical Installation

    Fix the brackets on the power supply subrack with bolts. Users can choose proper installation position according to actual instance. 2. Install the power supply subrack. Fix the subrack in the cabinet with fixing screws. The installation dimensions are shown in Figure 2-2. NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 11: Electrical Installation

    Refer to Table 2-5 to connect the input and output cables. Table 2-5 Connection descriptions of input and output cables Connection Cable From AC input cable AC power AC input terminals NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 12: Connecting Signal Cables

    The default associations of the relays are: critical alarm associating with DO1, and major alarm associating with DO2. A amplified view NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 13: Chapter 3 Installation Testing

    Check the system voltage and busbar polarity with a voltmeter. The voltage difference between the  measured value and displayed value should be less than ± 0.3V  Start and stop each rectifier by inserting and unplugging the rectifiers. Check their output voltages NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 14: Basic Settings

    The battery protection contactor should be open, and the ‘BLVD’ alarm should be displayed at the monitoring module Note: The monitoring module will give alarms approximately 10s after the alarms are triggered. Enter main menu Operation to view the alarm information NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 15: Final Steps

    If any defect is found in this equipment, inform the personnel responsible for the contract. If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the repairing center for fault analysis. NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 16: Chapter 4 Alarm Handling

    Load Fuse Alarm/ Or check the voltage at the alarm fuse. If the voltage is almost 0V, the fuse is normal. Batt Fuse Alarm Otherwise, the alarm loop is faulty. Please contact Emerson NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 17: Handling Rectifier Fault

    Ambient temperature too Decrease the ambient temperature or remove high or the inlet too close to the heat source a heat source NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 18 Be careful with the rectifier just pulled out from the system, as it could be very hot due to long-term operation. Do not let it slip away and get damaged. 4. Hold the rectifier handle, push the new rectifier into the slot and make sure the connection is good. NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 19 If the new rectifier passes all the above tests, the replacement is a success. 6. Push the handle back into the front panel to lock the rectifier. 7. Fix the fixing screw of the handle of the rectifier with a Phillips screwdriver. NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 20: Appendix 1 Technical Data

    100% rated current Rectifier Input voltage: 176Vac ~ 290Vac, rectifier max. output power: 50% rated power, Derate by input (45°C) 1000W Input voltage: 90Vac ~ 176Vac, rectifier output power: linear derating power NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 21 ROHS Compliant with R5 standard Size (W ×D System 437 × 289 × 43 ×H) (mm) Rectifier 86.5 × 241.1 × 40.8 Mechanical ≤ 7 System Weight (kg) ≤ 1.5 Rectifier NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 22: Appendix 2 Wiring Diagram

    Front pannel connection of the DU area DI/DO&TEMP Connector Of the SCU+ Controller. IB0 connector 橙色 紫色 红 色 蓝 色 棕色 绿 色 黑色 黄色 Back View Figure 1 Wiring diagram of the system NetSure 211 C23 Embedded Power Supply System User Manual...
  • Page 23: Appendix 3 Glossary

    Low Voltage Disconnection Miniature Circuit Breaker Ph-A Phase A Password Rect Rectifier Shunt coeff Shunt Coefficient Surge Protection Device SW Version Software Version System Temp Temperature Temp Comp Temperature Compensation Volt Voltage NetSure 211 C23 Embedded Power Supply System User Manual...

Table of Contents