When operating Emerson products, the operation personnel must observe the safety rules in the industry, the general safety points and special safety instructions specified in this book.
Page 3
IV. ESD Note The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs. Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the sensitive components.
Page 4
Others I. Safety Note Noti ce Warning When replacing power input fuses of monitoring module and power distribution units, use the same type fuses to meet the safety requirement. II. Sharp object Warning When moving equipment by hand, wear protective gloves to avoid injury by sharp object. III.
Chapter 1 Overview Chapter 1 Overview This chapter introduces model description, composition and configuration, and features of NetSure 211 C23 embedded power supply system (abbreviated as ‘system’ hereinafter). 1.1 Model Description The model description of the system is given in Figure 1-1.
The monitoring module is of network design. With an RS232 port, Ethernet, dry contacts and other communication ports provided, flexible networking is enabled to achieve remote monitoring and unattendance. The system has complete fault protection and fault alarm functions. NetSure 211 C23 Embedded Power Supply System User Manual...
The equipment should be unpacked and inspected after it arrives at the installation site. The inspection shall be done by representatives of both the user and Emerson Network Power Co., Ltd. To inspect the equipment, you should open the packing case, take out the packing list and check against the packing list that the equipment is correct and complete.
Fix the brackets on the power supply subrack with bolts. Users can choose proper installation position according to actual instance. 2. Install the power supply subrack. Fix the subrack in the cabinet with fixing screws. The installation dimensions are shown in Figure 2-2. NetSure 211 C23 Embedded Power Supply System User Manual...
Refer to Table 2-5 to connect the input and output cables. Table 2-5 Connection descriptions of input and output cables Connection Cable From AC input cable AC power AC input terminals NetSure 211 C23 Embedded Power Supply System User Manual...
The default associations of the relays are: critical alarm associating with DO1, and major alarm associating with DO2. A amplified view NetSure 211 C23 Embedded Power Supply System User Manual...
Check the system voltage and busbar polarity with a voltmeter. The voltage difference between the measured value and displayed value should be less than ± 0.3V Start and stop each rectifier by inserting and unplugging the rectifiers. Check their output voltages NetSure 211 C23 Embedded Power Supply System User Manual...
The battery protection contactor should be open, and the ‘BLVD’ alarm should be displayed at the monitoring module Note: The monitoring module will give alarms approximately 10s after the alarms are triggered. Enter main menu Operation to view the alarm information NetSure 211 C23 Embedded Power Supply System User Manual...
If any defect is found in this equipment, inform the personnel responsible for the contract. If repairing is needed, please fill in the FAILURE REPORT and send the report together with the defective unit to the repairing center for fault analysis. NetSure 211 C23 Embedded Power Supply System User Manual...
Load Fuse Alarm/ Or check the voltage at the alarm fuse. If the voltage is almost 0V, the fuse is normal. Batt Fuse Alarm Otherwise, the alarm loop is faulty. Please contact Emerson NetSure 211 C23 Embedded Power Supply System User Manual...
Ambient temperature too Decrease the ambient temperature or remove high or the inlet too close to the heat source a heat source NetSure 211 C23 Embedded Power Supply System User Manual...
Page 18
Be careful with the rectifier just pulled out from the system, as it could be very hot due to long-term operation. Do not let it slip away and get damaged. 4. Hold the rectifier handle, push the new rectifier into the slot and make sure the connection is good. NetSure 211 C23 Embedded Power Supply System User Manual...
Page 19
If the new rectifier passes all the above tests, the replacement is a success. 6. Push the handle back into the front panel to lock the rectifier. 7. Fix the fixing screw of the handle of the rectifier with a Phillips screwdriver. NetSure 211 C23 Embedded Power Supply System User Manual...
Front pannel connection of the DU area DI/DO&TEMP Connector Of the SCU+ Controller. IB0 connector 橙色 紫色 红 色 蓝 色 棕色 绿 色 黑色 黄色 Back View Figure 1 Wiring diagram of the system NetSure 211 C23 Embedded Power Supply System User Manual...
Low Voltage Disconnection Miniature Circuit Breaker Ph-A Phase A Password Rect Rectifier Shunt coeff Shunt Coefficient Surge Protection Device SW Version Software Version System Temp Temperature Temp Comp Temperature Compensation Volt Voltage NetSure 211 C23 Embedded Power Supply System User Manual...