Spec. No. 581127000 (Model 710
DIP Switch SW1
HW/
Shunt
Reserved
SW
Voltage
1
2
3
4
OFF
NA
ON
OFF OFF
OFF
NA
ON OFF
ON
NA
DIP Switch SW2
Reserved
1
2
3
4
NA
NA
Note 1: Setting for this system.
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NPBA
Shunt
Current
5
6
7
8
NA
ON
NA
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
Communications
Baud
Address
Rate
5
6
7
8
OFF OFF
OFF
OFF OFF
ON
OFF
ON
OFF
OFF
ON
ON
NA
ON
OFF
OFF
ON
OFF
ON
ON
ON
OFF
ON
ON
ON
OFF
ON
Optional SM-DU+ Board DIP Switch Settings
Chapter 3. Setting Jumpers and Switch Options
Shunt parameter is set through DIP switch.
Shunt parameter is set through software (note 1).
Shunt Voltage: 25mV (note 1)
Shunt Voltage: 50mV
Shunt Voltage: 60mV
Shunt Voltage: 75mV
Shunt Current: 500A (note 1)
Shunt Current: 100A
Shunt Current: 200A
Shunt Current: 300A
Shunt Current: 400A
Shunt Current: 1000A
Shunt Current: 1500A
Shunt Current: 2000A
Address 1# (Setting for SM-DU+ in this system)
Address 2#
Address 3#
Address 4#
Address 5#
Address 6#
Address 7#
Address 8#
19200 (note 1)
9600
Table 3-3
IM581127000
Issue AB, March 22, 2012
Description
of Status
Description
of Status
Page 35

Advertisement

Table of Contents
loading

This manual is also suitable for:

581127000

Table of Contents