Emerson NetSure 710NPBA Installation Instructions Manual page 115

+24v dc power system
Table of Contents

Advertisement

Installation Instructions
Spec. No. 581127000 (Model 710
Chapter 5. Installing the Modules and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
)
NPBA
6) Adjust the "IB2 Temp1 High 2" setpoint to 10 degrees below the temperature
recorded in step 2).
a) Requirement: An "IB2 Temp1 High 2" alarm is displayed.
b) Requirement: External "Relay 12 High 2 Battery Temperature Alarm"
(requires EIB Interface Board to be installed in the system) activates.
7) Using the Web Interface, adjust the "IB2 Temp1 High 2" setting to the value
recorded in step 5).
8) Using the Web Interface, adjust the "IB2 Temp1 High 1" setting to the value
recorded in step 3).
a) Requirement: No alarms are displayed on the Web Interface screen.
b) Requirement: The external alarm deactivates.
IM581127000
Issue AB, March 22, 2012
Page 107