5
PARAMETER SETTINGS

5.2 Remote I/O Station Parameter Settings

5.2.1 Remote I/O station possible parameter settings

Category
Module synchronization
PLC system
Points occupied by empty slot
Error check
PLC RAS
Operating mode when there is an error
1
Remote I/O switch setting
Assignment method
Operational settings
Forwarding parameter between devices
I/O assignment
I/O assignment
Standard setting
5 - 33
For remote I/O stations, set up the PLC parameters, network parameters, and remote
password on the remote I/O module as needed.
POINT
After writing the parameters to the remote I/O module, reset it to enable the
parameters that have been set. To reset the remote I/O module, use the reset
switch on the module or power OFF and then ON the remote I/O station.
The following parameters are set as needed on the remote I/O station and written to
the remote I/O module.
If settings are not needed, the remote I/O station operates using the remote I/O module
default settings so there is no need to write the parameters to the remote I/O module.
(1) PLC parameters
The remote I/O module can set the PLC parameters in the same manner as the
CPU module. However, only the required items can be set as a remote I/O
station.
Item
Synchronizes intelligent module's pulse
up
Points occupied by empty slot
Carry out fuse blown check
Verify module
Fuse blown
Module verify error
Remote I/O switch setting (For future
expansion)
Points/Start
Start/End
Device name
Points/Start
Start/End
Type
Model name
Points
StartXY
Switch setting
Switches 1 to 5
Error time output
mode
Detailed setting
H/W error time PLC
operation mode 2
I/O response time
Base model name
Power model name
Extension cable
Slots
Base mode
MELSEC-Q
Default
Selected
16 points
Selected
Selected
Stop
Stop
Start/End
Blank
Blank
Blank
Clear
Stop
10ms or 0.2ms
Blank
Auto