Mitsubishi Electric MELSEC Q Series Reference Manual page 198

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6
PROGRAMMING
No.
Name
1
SW0070
(112)/
SW0071
Baton pass status
(113)/
of each station
SW0072
(114)/
SW0073
(115)
1
SW0074
(116)/
SW0075
Cyclic transmission
(117)/
status of each
W0076
station
(118)/
SW0077
(119)
1: Valid only when SB0047 is off. When it turns on (error), the last data are retained.
6 - 3
Description
Stores the baton pass status of each station (Including the host).
<Online>
0: Normal (including the stations with the maximum station
number and smaller numbers as well as reserved stations)
1: Abnormal
<Offline test>
0: Normal
1: Abnormal (including the stations with the maximum station
number and smaller numbers as well as reserved stations)
b15 b14 b13 b12
16
15
14
13
SW0070
SW0071
32
31
30
29
48
47
46
45
SW0072
SW0073
64
63
62
61
Stores the cyclic transmission status of each station (including the
host).
0: Executing cyclic transmission (including the station with the
maximum station number and smaller number as well as
reserved stations)
1: Cyclic transmission not executed
b15 b14 b13 b12
SW0074
16
15
14
13
SW0075
32
31
30
29
SW0076
48
47
46
45
SW0077
64
63
62
61
If a CPU module installed together with QJ71LP21S-25 is turned
OFF, detection of a data link error may take more time than usual.
For immediate detection of a data link error, program an interlock
using the link relay (LB) in each station's send range. For details,
refer to the Q corresponding MELSECNET/H Network System
Reference Manual (PLC to PLC network).
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
to
37
36
35
34
33
to
53
52
51
50
49
Numbers 1 to 64 in the above table
indicate the station numbers.
to
b4
b3
b2
b1
b0
to
5
4
3
2
1
to
21
20
19
18
17
to
37
36
35
34
33
to
53
52
51
50
49
Numbers 1 to 64 in the above table
indicate the station numbers.
[Availability column] Optical: optical loop, Coaxial: coaxial bus
Use permitted/prohibited
Remote
Control
Normal
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
: Available,
: Not available
MELSEC-Q
Remote I/O
master
station
station
6 - 3