Mitsubishi Electric MELSEC Q Series Reference Manual page 28

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

1 OVERVIEW
QCPU
Master module
Link register W
Link register LW
Refresh
QCPU
Master module
Z.REMTO
1 - 6
(3) Providing versatile communication services
(a)
Reading data from and writing data to intelligent function modules mounted
on remote I/O stations are easy.
There are four methods available for reading and writing.
1)
Use GX Configurator to make the initial settings and automatic refresh
settings with intelligent function module parameters, and write them
into the remote I/O module in the remote I/O station.
By refreshing the intelligent function module data to the link register W
of the remote I/O module based on the auto refresh settings, the
remote master station can read/write refreshed data by cyclic
transmission.
Remote master station
QCPU
Intelligent function
module parameters
• Initial settings
• Automatic refresh
settings
2)
Link dedicated instructions can be used to directly read from or write to
the buffer memory of the intelligent module.
• REMFR instruction: Reads data from the buffer memory of the
remote I/O station intelligent function module.
• REMTO instruction: Writes data to the buffer memory of the remote
I/O station intelligent function module.
Remote master station
QCPU
Remote I/O station
Intelligent function module
LW
GX
Configurator
REMTO
Remote I/O station
Intelligent function module
MELSEC-Q
Intelligent
Remote I/O module
function module
Link register W
Buffer memory
Refresh
Intelligent
Remote I/O module
function module
Buffer memory
REMTO
1 - 6