Mitsubishi Electric MELSEC Q Series Reference Manual page 279

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

7
APPLICATION FUNCTIONS
Error code Error message LED status
3400
REMOTE
PASS. ERR.
3401
REMOTE
PASS. ERR.
7 - 43
(5) Error codes detected by remote I/O module
ERR. LED:
The head I/O number of the target
on
module in the remote password file is
set to other than 0
ERR. LED:
Any of the following modules is not
on
mounted on the slot specified for the
head I/O number of the remote
password.
• Serial communication module of
function version B or later
• Ethernet module of function version B
or later
(6) Cautions when setting a remote password
(a)
If the starting I/O No. is changed after the remote password is set, the
previous remote password set with the Ethernet module/serial
communication module becomes invalid.
(b)
Only the remote password set for the directly connected module can be
canceled (unlocked) by remote operation of GX Developer. (The remote
password for the indirectly connected module cannot be canceled by
remote operation.)
Description
to 0FF0
.
H
H
MELSEC-Q
Measures
Change the head I/O number of the
target module to within the 0
range.
Mount any of the following modules in
the position specified for the head I/O
number of the remote password.
• Serial communication module of
function version B or later
• Ethernet module of function version B
or later
to 0FF0
H
H
7 - 43

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents