Mitsubishi Electric MELSEC Q Series Reference Manual page 234

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6
PROGRAMMING
No.
Send/receive device number valid/invalid
SB01C8
status
No.
System switching monitoring time setting
SB0018
valid flag
Host station's redundant function support
SB0041
information
6 - 39
(c) Checking device ranges of the multiplexed remote master and
sub-master stations
1)
When Send LY/Receive LX device numbers of the multiplexed
remote master and sub-master stations (SW01C8 to SW01CF)
become valid, Send/receive device number valid/invalid status
(SB01C8) is turned ON.
2)
The send/receive device numbers of the multiplexed remote master
and sub-master stations can be checked in SW01C8 to SW01CF.
Description
(12) Checking the redundant multiplexed remote master function
support and setting
With link special relays (SB) and link special registers (SW), whether the
multiplexed remote master function is supported can be checked and relevant
settings can be configured.
1)
When the network module supports the redundant multiplexed remote
I/O networks, Host station's redundant function support information
(SB0041) is turned ON.
2)
To set the time taken from detection of a data link stop until system
switching is requested in the redundant system, set a time value in
System switching monitoring time setting (SW0018).
3)
If System switching monitoring time setting valid flag (SB0018) is
turned ON, System switching monitoring time setting (SW0018) is
enabled.
Description
No.
SW01C8
Send LY device number
SW01C9
Receive LX device number
SW01CC
Send LB device number
SW01CD
Receive LB device number
SW01CE
Send LW device number
SW01CF
Receive LW device number
No.
SW0018
System switching monitoring time setting
MELSEC-Q
Description
Description
6 - 39

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents