Mitsubishi Electric MELSEC Q Series Reference Manual page 95

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3 - 39
(4) SB/SW when a communication error station/communication stop
station occurs on the network
The status of whether there are any communication error/communication stop
stations on the network can be checked with the link special relay/register
(SB/SW).
Use them as interlocks for programs.
Link special
relay/register
SB0047
Shows the baton pass execution status of the host.
SB0049
Shows the data link status of the host.
Shows the baton pass execution status of all
stations (including the host). However, it only shows
SB0070
the status for the number of stations set with
parameters.
Shows the baton pass execution status of each
SW0070 to
station.
0073
Each bit corresponds to the status of each station.
Shows the cyclic transmission status of all stations
(including the host). However, it only shows the
SB0074
status for the number of stations set with
parameters.
SW0074 to
Shows the cyclic transmission status of each station.
0077
Each bit corresponds to the status of each station.
Link special relays and registers
Description
MELSEC-Q
Signal status
Off
On
The baton
The baton
pass is being
pass is
executed
stopped
Normal
Abnormal
Occurrence
The baton
of
pass is being
communicati-
executed on
on stop
all stations
station
The baton
The baton
pass is being
pass is
executed
stopped
Occurrence
All stations
of abnormal
normal
station
Normal
Abnormal
3 - 39