6
PROGRAMMING
No.
SB00A8
Online test instruction
SB00A9
Online test completion
No.
SB00AA
Online test response instruction
SB00AB
Online test response completion
6 - 33
(7) Checking the online test status
The test status is checked through LED of the network module main frame, but it
also can be checked with link special relay (SB) and link special register (SW).
(Refer to Section 4.10.)
(a) Requesting side
1)
When the online test is instructed, Online test instruction (SB00A8) is
turned ON.
An online test item and a faulty station number are stored in Online
test execution item/faulty station (requesting side) (SW00A8).
2)
Upon completion of the online test, Online test completion (SB00A9) is
turned ON.
The online test result is stored in Online test result (requesting side)
(SW00A9).
Description
(b) Responding side
1)
When a response is made to an online test request from the
requesting side, Online test response (SB00AA) is turned ON.
An online test item is stored in Online test execution item (responding
side) (SW00AA).
2)
Upon completion of the online test, Online test response completion
(SB00AB) is turned ON.
The online test result is stored in Online test result (responding side)
(SW00AB).
Description
No.
Online test execution item/faulty station
SW00A8
(requesting side)
SW00A9
Online test result (requesting side)
No.
Online test execution item (responding
SW00AA
side)
SW00AB
Online test result responding side)