Mitsubishi Electric MELSEC Q Series Reference Manual page 114

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

3
SPECIFICATIONS
3 - 58
(6) Transmission delay time formula
The transmission delay time is calculated based on the following system design
and conditions.
(System design, conditions)
1)
CPU module: Q06HCPU
2)
Total number of remote I/O stations: 8
3)
Number of link devices: LX = LY = 1024 points, LB = LW = 0 point,
SB = SW = 512 points
4)
Remote master station CPU module scan time: 1 ms
5)
Communication speed: 10 Mbps
6)
File register not used.
7)
Transient transmission not used.
8)
Remote master station mounts the master module to the main base unit.
9)
All remote I/O stations only use the I/O module.
10) The link device per each remote I/O station is LX = LY = 128 points.
11) Link scans are performed in synchronization with sequence scans.
(END synchronization)
<Constants when a master module is mounted to the main base unit.>
CPU type
Q06HCPU
(a)
Link refresh time (m)
m = KM1 + KM2
= 0.13 + 0.41
= 0.41 [ms]
(b)
Link scan time (LS)
LS = KB + (0.45
(LW
16)} /16
+ {LXM R + LBM R + (LWM R
+ (T
= 4.0 + (0.45
+ {1024 + 0 + (0
+ {1024 + 0 + (0
+ (0
= 11.8 [ms]
(c)
I/O refresh time
T
= XK/16
RIOR
+ YZ/16
= 128/16
= 0.024 [ms]
Constant
KM1
0.13
{(LB + LX + LY + SB) /16 + LW + SW} + E
10
-3
{(0 + 1024 + 1024 + 512) /16+0+512}+0
total number of remote I/O stations) + {LX + LY + LB +
16)} /8
0.001 + KR + {LYM R + LBM R + (LWM R
0.0003
0.001) + (F
4)
8) + {1024 + 1024 + 0 + (0
16)} /16
16)} /16
0.001) + (0
4)
0.0016 + XZ/16
0.0022
0.0016 + 0 + 128/16
MELSEC-Q
KM2
–3
(
10
)
0.41
16)} /16
0.0003
16)} /8
0.0003
0.0003
0.0024 + YK/16
0.0014
0.0014 + 0
KM3
–3
(
10
)
0.53
0.001 + 3.9
3 - 58