Program Example When Not Using Gx Configurator - Mitsubishi Electric MELSEC Q Series Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

6
PROGRAMMING

6.4.2 Program example when not using GX Configurator

6 - 15
POINT
Execution of the REMFR/REMTO instruction needs several scans.
Therefore, the execution result of the REMFR/REMTO instruction cannot be
synchronized with operations of the I/O signals.
When reading a digital output value on a Q64AD after changing the operating
condition during operation, be sure to read the A/D conversion completed flag
(buffer memory address 10) at the same time.
Also, for the case of changing the operating condition, insert an interlock to prevent
the execution of the REMFR instruction.
(1) Setting for the CPU module on the remote master station
• Network type
• Starting I/O No.
• Network No.
• Total stations
• Mode
• Network range assignment:
• Refresh parameters:
(2) Setting for the remote I/O module
In GX Developer, set the intelligent function module switches. (Refer to Section
6.4 (1).)
: MNET/H (Remote master)
: 0000
H
: 1
: 1
: Online
MELSEC-Q
6 - 15