3.7

Others

Device station parameter automatic setting

This function saves parameters of the device station in the master station, and automatically set the parameters when the
device station is connected or returned to the network.
As the parameters are changed on the device station side, the saved parameters of the master station side are automatically
updated.
Automatic update of saved parameters is available for the firmware version "1.001" or later.
Device station parameter automatic setting from the master station
1.
Parameters of the device station set using the engineering tool are saved in the memory of the CPU module in the
master station or the SD memory card by writing.
2.
When the device station is connected or returned to the network by power-on, saved parameters are automatically set
from the master station.
(A)
No.0
 Save parameter (A) of the device station to the CPU module in the master station.
 When the device station is returned/connected, saved parameter (A) is automatically set from the master station to the device station.
• The master station starts data link with the device station after parameters of the device station are
automatically set.
• The device station parameter automatic setting is also executed for device stations set as reserved stations.
Automatic update of saved parameter
1.
If parameters on the device station side are changed by the engineering tool or SLMP, the parameters of the device
station that are saved in the memory of the CPU module or the SD memory card are automatically updated.
2.
When the module of the device station has been replaced, updated parameters are automatically set from the master
station by resetting the master station or turning its power off and on.
Õ
(B)
(A)
(B)
No.0
No.0
 Parameter (A) of the device station is changed to (B) by SLMP.
 Saved parameter (A) of the CPU module on the master station is automatically updated to parameter (B).
Ò
Ó
(A)
Ô
(A)
No.2
SLMP
No.2
3
3 FUNCTIONS
51
3.7 Others

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-40ssc-gMelsec iq-f fx5-80ssc-g

Table of Contents