Mitsubishi Electric MELSEC Q Series Reference Manual page 352

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

APPENDICES
No.
Name
3
CPU RUN status of each
SB0084
station
(132)
3
CPU RUN status of the
SB0085
remote master station
(133)
3
Remote sub-master
SB0086
station CPU RUN status
(134)
3
4
CPU operation status of
SB0088
each station (2)
(136)
3
External power supply
SB008C
information
(140)
3
Module type of each
SB008D
station
(141)
SB0090
Host loop status
(144)
3
SB0091
Forward loop status
(145)
3
Forward loop status of
SB0092
remote master station
(146)
3: Valid only when SB0047 is off. When it turns on (error), the last data are retained.
4: Minor errors are the type of errors that do not affect the CPU operation. (Refer to Section 8.3.3)
6: Available only in the remote sub-master station.
App - 10
Table 2 Link special relay (SB) list (Continued)
Description
Indicates the CPU RUN status of each station.
Off: All stations are in the RUN or STEP RUN status
On: Stations in the STOP or PAUSE status exist
(including the host)
When some stations are in the STOP or PAUSE status, each
station status can be checked in CPU RUN status of each station
(SW0084 to SW0087).
Depending on the timing of the link refresh, CPU RUN status of
each station (SW0084 to SW0087) and the update may be offset
by one sequence scan.
Indicates the CPU run status of remote master station.
Off: Run or STEP RUN status
On: STOP or PAUSE status
Indicates the CPU status of the multiplexed remote sub-master
station.
Off: RUN or STEP RUN status
On: STOP or PAUSE status
Indicates the operation status of each station's CPU or of each
remote I/O station (including the host station).
Off: All stations normal
On: Stations with minor errors exist
If any station with a minor error exists, the status of each station
can be checked in CPU operation status of each station (2)
(SW0088 to SW008B).
Depending on the timing of the link refresh, CPU operation status
of each station (2) (SW0088 to SW008B) and the update may be
offset by one sequence scan.
Indicates the information of the external power supply (including
the host).
Off: All stations are without external power supply
On: Stations with external power supply exist
When any station with external power supply exists, the status of
each station can be checked in Power supply status of each
station (SW008C to SW008F).
Depending on the timing of the link refresh, Power supply status
of each station (SW008C to SW008F) and the update may be
offset by one sequence scan.
Indicates the module type of each station.
Off: All stations are NET/10 type modules
On: NET/10H type modules exist
Indicates the host's loop status.
Off: Normal
On: Abnormal
When an error is identified, the error details can be checked by
Loopback information (SW0090).
Indicates the status of stations connected to the forward loop.
Off: All stations normal
On: Faulty stations exist
When any faulty station exists, the status of each station can be
checked in Forward loop status of each station (SW0091 to
SW0094).
Depending on the timing of the link refresh, Forward loop status
of each station (SW0091 to SW0094) and the update may be
offset by one sequence scan.
Indicates the forward loop status of the remote master station.
Off: Normal
On: Error
MELSEC-Q
Availability
Remote
Control
Normal
master
station
station
station
Optical Coaxial Optical Coaxial Optical Coaxial Optical Coaxial
Remote I/O
station
6
App - 10