7
APPLICATION FUNCTIONS
7 - 19
(d)
The intelligent function modules such as serial communication module,
Ethernet module which are mounted to the remote I/O stations can access
the station that is currently performing master operation in the MELSEC
communication protocol.
Access Destination
Multiplexed remote master station
(Station No. 0)
Multiplexed remote sub-master station
Master operating station
(e)
The outputs of the remote I/O stations are held while master operation is
being switched from the multiplexed remote master station to the
multiplexed remote sub-master station.
Multiplexed remote
master station
Remote I/O station Remote I/O station
Multiplexed remote
master station
Master operation
After switching, outputs are cleared.
Remote I/O station Remote I/O station
POINT
Start up the multiplexed remote sub-master station last (after the data link of the
multiplexed remote master station and remote I/O stations is established).
To start from a data link using the multiplexed remote master station independently
of the startup order, do not set Total stations and Setup common in the parameters
of the multiplexed remote sub-master station.
REMARKS
The multiplexed remote master station and multiplexed remote sub-master station
cannot be mounted together on a single programmable controller CPU.
Target Station Number to Be Set
7D
H
Multiplexed remote sub-master station No.
7E
H
Multiplexed remote
sub-master station
Master operation
Remote I/O station
Multiplexed remote master station returns to system
Multiplexed remote
sub-master station
Information
Sub-master operation
transfer
Remote I/O station