Setup Confirmation Test - Mitsubishi Electric MELSEC Q Series Reference Manual

Q corresponding melsecnet/h network system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

4
SETTING AND PROCEDURE BEFORE OPERATION

4.10.2 Setup confirmation test

4 - 34
This test checks the switch setting of a network module.
The following items can be checked.
1)
Control station overlap status (This check is not performed on remote
I/O network.)
2)
Station number duplication status
3)
Network No. consistency check (Whether the network number set for
the station where GX Developer is connected matches the network
number set in network parameter of the host station.)
GX Developer
When the setup confirmation test is performed using GX Developer connected to the
remote master station in the system above, the following screen appears.
The result shows that the station number 1 has a station No. duplication error.
(Parameter settings)
Remote master station
Station
Station
No. 0
No. 2
Station
Station
No. 1
No. 7
Duplicate error
Reserved station Reserved station
Station
No. 3
Network No. 1
Station
No. 1
Duplicate error
MELSEC-Q
Station
No. 4
Station
No. 5
4 - 34