AS-i 3.0 Command Interface
Commands of the Command Interface
Safety Control-Status
length
2 byte E
1 byte A
4 byte E
1 byte A
6 byte E
2 byte A
8 byte E
2 byte A
10 byte E
3 byte A
12 byte E
3 byte A
14 byte E
4 byte A
16 byte E
4 byte A
Information!
Additional information on diagnostics via Safety Control Status in PROFIBUS Gate-
ways can be found in system manual "AS-i 3.0 PROFIBUS Gateways with integr.
safety monitor".
Alternatively, you can read out the Safety Control Status via the transparent input
data of the AS-i base address of the monitor (for OSSD 1-8) on the profile 7.5.5
Channel '0' of the transparent input data describes the state of the two AS-i cir-
cuits (traffic light status).
The upper 8 bits describe the state of AS-i circuit 2, the lower the state of AS-i cir-
cuit 1.
Channels 1 and 2 contain the colors of release circuits 1 – 8.
Channel 3 displays summary information about red and yellow
the reference to release circuits.
description
Safety Ctrl/Status (OSSD 2)
Safety Ctrl/Status (OSSD 4)
Safety Ctrl/Status (OSSD 6)
Safety Ctrl/Status (OSSD 8)
Safety Ctrl/Status (OSSD 10)
Safety Ctrl/Status (OSSD 12)
Safety Ctrl/Status (OSSD 14)
Safety Ctrl/Status (OSSD 16)