Page 2
VBP-HH1-V3.0* With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation...
All products were developed and manufactured under observance of the applicable European standards and guidelines. Note! A Declaration of Conformity can be requested from the manufacturer. The product manufacturer, Pepperl+Fuchs GmbH, 68307 Mannheim, has a certified quality assurance system that conforms to ISO 9001. ISO9001...
If serious faults occur, stop using the device. Secure the device against inadvertent operation. In the event of repairs, return the device to your local Pepperl+Fuchs representative or sales office. When packing the device for storage or transport, use materials that will protect the device from bumps and impacts and protect against moisture.
VBP-HH1-V3.0* Notes on disposal Notes on disposal Electronic waste is hazardous waste. When disposing of the equipment, observe the current statutory requirements in the respective country of use, as well as local regulations. Do not dispose of storage batteries with the household refuse.
VBP-HH1-V3.0* Product Description Product Description AS-Interface Specification 3.0 In 2004, the AS-Interface Association defined the AS-Interface Specification 3.0 as a backwards-compatible extension, while retaining the protocol and physical structure. AS-Interface Specification 3.0 gives the user important advantages: The number of possible network slaves is increased to 62. This is ■...
VBP-HH1-V3.0* Product Description 4.4.1 AS-Interface-Anschlussadapter Figure 4.2 The AS-Interface connection adapter on the top of the addressing device is used to connect AS-Interface nodes (sensors, actuators, and interface modules) to the addressing device. The following devices and models can be connected directly...
Page 11
VBP-HH1-V3.0* Product Description Address and data display Depending on the operating mode, two digits and the letters A and B are used to display various information in this area of the display. The address of the currently selected AS-Interface node differs according ■...
VBP-HH1-V3.0* Product Description 4.4.3 Button assignment Button Description Set values (e.g.slave address, ID1 data, slave parameters, slave data), change of operating mode Set values (e.g. slave address, ID1 data, slave parameters, slave data) The function depends on the operating mode: transfer of a new slave address to the slave (ADDR) ■...
VBP-HH1-V3.0* Product Description Accessories Various accessories are available. 4.5.1 External power supply Product Product name VAN-115/230AC-K21-EFD AS-Interface power supply V1S-TEE-V1/V1S T-splitter for the connection of an external power supply (V1 plug) and an AS-Interface node (M12 socket) V1-W-2M-PVC Cable with V1 socket and open end for connection of the power supply 4.5.2...
VBP-HH1-V3.0* Commissioning Commissioning Preparation The addressing device battery is delivered fully charged. Nevertheless, as a result of self-discharge, the charge may not be sufficient to operate the addressing device. Therefore, we recommend that you charge the battery for at least 24 hours prior to commissioning.
VBP-HH1-V3.0* Commissioning Switching on the addressing device 1. Connect an AS-Interface node. 2. Briefly press the button. The addressing device switches on in theAddressing operating mode and shows the address of the current AS-Interface node. Changing operating mode You have several options to set the various operating modes.
VBP-HH1-V3.0* Operation Operation Addressing operating mode The addressing is divided into 3 individual procedures. The following table shows the individual processes: Note! When addressing AS-Interface slaves connected to the handheld, make sure that the address 0 is not occupied. Otherwise, an error message may occur.
VBP-HH1-V3.0* Operation Setting the target address Set the target address using the buttons. Addresses marked as occupied The already assigned addresses are stored in the addressing device in a list of assigned addresses and shown in the address field of the display as a non- flashing number.
VBP-HH1-V3.0* Operation Write ID1 Code Note! The value of the ID1 Code ranges from 0 to 15 for standard AS-Interface slaves and from 0 to 7 for A/B slaves. To write an ID1 Code to the active AS-Interface slave, proceed as follows: 1.
VBP-HH1-V3.0* Operation Set Slave Parameter operating mode In the operating mode Read/write slave data, the slave parameter value activates the data transmission from the addressing device to the AS-Interface slave. The standard value is 15 for standard AS-Interface slaves and 7 for A/B slaves.
Page 20
VBP-HH1-V3.0* Operation Checking output data You can check the set output data by briefly pressing the button. The set output data are displayed. No data is transferred to the slave. The set output data value is temporarily stored in the handheld. The output data value is shown on the display as long as you do not press the buttons.
Page 21
VBP-HH1-V3.0* Operation All other complex communication protocols are not supported and are handled by the addressing device as standard AS-Interface slaves. Safety Code (AS-Interface Safety At Work) As soon as both input channels of an AS-Interface safety slave are active, a cyclic sequence of 8 x 4 bits is transmitted to the addressing device.
VBP-HH1-V3.0* Error messages Error messages The following messages can appear in the addressing device display. Error code Meaning Description Remedy AS-Interface overload Current consumption of Connect an external the AS-Interface slaves power supply. connected to the addressing device is too high.
VBP-HH1-V3.0* Technical data Technical data Figure 8.1 General specifications VBP-HH1-V3.0 VBP-HH1-V3.0-110V Operating mode plug-in charging unit, 230 V Power adapter 120 V AC, AC, included in the delivery included with delivery package AS-Interface V3.0 specification Indicators/operating means Display LC display...
Page 24
VBP-HH1-V3.0* Technical data Compliance with standards and directives Directive conformity Low Voltage Directive EN 61558-1:2005 , EN 61558-2-6:1997 2006/95/EC EMC Directive EN 61326-1:2006 , EN 61000-6-4:2007 2004/108/EC Standard conformity Noise immunity EN 61326-1:2006 Emitted interference EN 61000-6-4:2007 Protection degree EN 60529:2000...