Get Transm.err.counters (Get_Tecb) - Pepperl+Fuchs AS-I 3.0 Manual

Command interface
Table of Contents

Advertisement

AS-i 3.0 Command Interface
Commands of the Command Interface
4.4.12

Get transm.err.counters (GET_TECB)

Information!
In order to get the real number of transcription errors, multiply the value with 2.
With this call, the counts of the error counters for B-slaves are being read out (see
chap. "Advanced diagnostic for AS-i Masters" in the manual of your AS-i Master).
With every reading out of the counts, the error counters will be restarted.
The counts are being read out via the corresponding host interface and will be de-
leted with every read access. The counter´s value is limited to 254. 255 will cause
a counter overflow.
The counts could be independent of the counters, which are displayed in the dis-
play of the gateway.
byte
1
2
byte
1
2
3
4
...
34
58
7
6
5
2
2
2
T
7
6
5
2
2
2
T
Request
4
3
2
2
64
16
circuit
Response
4
3
2
2
64
16
result
APF
slave 1B
...
slave 31B
2
1
0
2
2
2
Tab. 4-98.
2
1
0
2
2
2
Tab. 4-99.