Pepperl+Fuchs AS-I 3.0 Manual page 165

Command interface
Table of Contents

Advertisement

AS-i 3.0 Command Interface
Command Interface Examples
3.
Read response (data part 1):
byte 1
byte 2
byte 3
byte 4
byte 5
byte 1
byte 2
byte 3
byte 4
byte 5
byte 6
byte 7
byte 8
byte 9
byte 10
byte 11
byte 12
byte 13
byte 14
byte 15
...
byte 36
byte 37
byte 38
4.
Read response (data part 2):
byte 1
byte 2
byte 3
byte 4
byte 5
request
0x4F (RD_ACYC_TRANS)
0x80 (master 1)
0x00 (integrated safety monitor)
0x00 (puffer index high)
0x00 (puffer index low)
response
0x4F (RD_ACYC_TRANS)
0x80 (OK)
0x0A (safety monitor diagnostics)
0x01 (length of the response buffer high)
0x06 (length of the response buffer low) 262
0x00 (fixed)
state of monitor
state of OSSD1
state of OSSD2
number of devices "not-green"
reserved
0x20 (device index 32)
device color 32
0x21 (device index 33)
device color 33
0x2C (device index 44)
device color 44
0x2D (device index 45)
request
0x4F (RD_ACYC_TRANS)
0x00 (master 1)
0x00 (integrated safety monitor)
0x00 (puffer index high)
0x24 (puffer index low) 36
Tab. 5-339.
Tab. 5-340.
Tab. 5-341.
165