Pepperl+Fuchs AS-I 3.0 Manual page 160

Command interface
Table of Contents

Advertisement

AS-i 3.0 Command Interface
Command Interface Examples
Example above:16-bit module at address 4 ⇒ Set bit 4/byte 0:
byte 1
byte 2
byte 3
byte 4
byte 5
...
byte 11
byte 12
byte 1
byte 2
...
byte 12
No result because toggle bit = 0.
Setting the toggle bit:
byte 1
byte 2
byte 3
byte 4
byte 5
...
byte 11
byte 12
byte 1
byte 2
byte 3
...
byte 12
The new list of protected slaves (LPS) is written.
160
request: SET_LPS
29
(SET_LPS)
hex
00
(T = 0, master 1, single master)
hex
00
hex
10
(LDS byte 0)
hex
00
(LDS byte 1)
hex
...
00
(LDS byte 7)
hex
00
hex
response
00
(or old values)
hex
00
(or old values)
hex
...
00
(or old values)
hex
request: SET_LPS
29
hex
80
(T = 1, master 1, single master)
hex
00
hex
10
(LDS byte 0)
hex
00
(LDS byte 1)
hex
...
00
(LDS byte 7)
hex
00
hex
response
29
hex
80
(T = 1, result = 0)
hex
00
(or old values)
hex
...
00
(or old values)
hex
Tab. 5-319.
Tab. 5-320.
Tab. 5-321.
Tab. 5-322.

Advertisement