Summary of Contents for Pepperl+Fuchs Viator HM-PF-USB-010031
Page 1
PROCESS AUTOMATION MANUAL Viator® USB HART Interface HM-PF-USB-010031...
Page 2
Viator® USB HART Interface With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"...
Viator® USB HART Interface Contents 1 Introduction............4 Content of this Document ..........4 Manufacturer ..............5 Target Group, Personnel ...........5 Symbols Used ..............6 2 Overview............8 3 Directive Conformity........9 4 Technical Data..........10 USB Pin Connections .............12 5 Getting Started..........13 Hardware and Software Requirements ......13 Check Your Viator USB HART Interface Package ...13 Connecting to a HART Field Device .......14 Standby and Hibernate Power Saving Modes....16...
Viator® USB HART Interface Introduction Introduction Content of this Document This document contains information that you need in order to use your product throughout the applicable stages of the product life cycle. These can include the following: Product identification Delivery, transport, and storage Mounting and installation Commissioning and operation Maintenance and repair...
EU-type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Additional documents Manufacturer Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany Internet: www.pepperl-fuchs.com Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator.
Viator® USB HART Interface Introduction Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation. Prior to using the product make yourself familiar with it. Read the document carefully.
Page 7
Viator® USB HART Interface Introduction Warning! This symbol indicates a possible fault or danger. Non-observance may cause personal injury or serious property damage. Caution! This symbol indicates a possible fault. Non-observance could interrupt the device and any connected systems and plants, or result in their complete failure. Informative Symbols Note This symbol brings important information to your attention.
PCs. The interface adheres to the USB 2.0 standard. The Viator USB HART Interface Software Driver included on the Pepperl+Fuchs website (http://www.pepperl-fuchs.com/cgi- bin/db/doci.pl?ShowProductDocByPartNo=70133892&LanId=ENU) provides the link between the USB port and the HART communication software by generating a virtual communications port.
Viator® USB HART Interface Directive Conformity Directive Conformity Europe Directive 2014/30/EU EN 61326-1:2013 EN 62368-1:2014-08 Directive 2011/65/EU (RoHS) EN IEC 63000:2018...
Viator® USB HART Interface Technical Data Technical Data Supply Input current 11 mA at 5 V Power supply Powered by USB port, No external power required Interface Interface type USB port Output Signal 0.5 ± 0.1 Vpp trapezoidal wave at 1200/2200 Hz, 24 VDC at 40 mA to device Galvanic isolation Output/interface...
Page 11
Viator® USB HART Interface Technical Data System requirements Operating system 32-bit XP, 32-bit Vista, 32-bit and 64-bit Windows® 7, and Windows® 10 Ambient conditions Operating -20 ... 50 °C (-4 ... 122 °F) temperature Storage -20 ... 60 °C (-4 ... 140 °F) temperature Relative humidity 0 ...
Viator® USB HART Interface Technical Data Mechanical specifications Material Polycarbonate Dimensions 75 mm x 33 mm x 15 mm Cable length 1.8 m 2-strand wire terminating in 2 test clips, 15.2- cm cable terminating in 1 USB type A connector Supplementary information Supplementary Observe the certificates, declarations of conformity,...
Viator® USB HART Interface Getting Started Getting Started Hardware and Software Requirements Viator USB HART Interface, HM-PF-USB-010031 Computer with one ore more USB ports Windows® operating system (32-bit XP, 32-bit Vista, 32-bit and 64-bit Windows® 7, and Windows® 10) HART application software for communication with HART field devices Note HART communication software must be capable of recognizing...
Viator® USB HART Interface Getting Started Connecting to a HART Field Device The interface has an integrated USB cable with a male A plug for connection to the computer, and it has an integrated 6-foot cable with 2 test clips. The interface connection to the HART network is transformer isolated and polarity insensitive.
Page 15
Viator® USB HART Interface Getting Started Figure 5.1 Connect the test clips 1. across the HART field device or 2. across the load resistor.
Viator® USB HART Interface Getting Started Caution! Do not connect the Viator interface across the power supply! This will not allow communication with the HART field device. Standby and Hibernate Power Saving Modes The Viator USB Interface driver supports all portable computer power saving modes.