Rd_74_75_Id - Pepperl+Fuchs AS-I 3.0 Manual

Command interface
Table of Contents

Advertisement

AS-i 3.0 Command Interface
Commands of the Command Interface
4.2.4

RD_74_75_ID

With this function the ID string of a slave according to profile S-7.4 or the 16-bit
slave configuration according to profile 7.5 is being read. Since the string can be
longer than the command interface, it is written into the buffer. The content of the
buffer can read in parts from index i.
The first byte of the buffer is the length of the read string.
If i ≡ 0, the string is being read from the slave, otherwise the function responses
out of the memory, the data can be read consistently.
byte
1
2
3
4
byte
1
2
3
...
n+2
By a 7.5 slave is the request always 1. The response byte contains the cyclic 16-
bit slave configuration according to S-7.5 profile (analog/transparent bits are can-
celled). If the response is 08
could not be detected.
22
7
6
5
2
2
2
T
7
6
5
2
2
2
T
16
Request
4
3
2
2
5C
16
circuit
slave address
i
Response
4
3
2
2
5C
16
result
buffer byte i
...
buffer byte i+n-1
, that means that the cyclic 16-bit configuration
2
1
0
2
2
2
Tab. 4-27.
2
1
0
2
2
2
Tab. 4-28.