AS-i 3.0 Command Interface
Commands of the Command Interface
4.8.3.2

Enhanced diagnostic

Since the "Safety at Work" monitor diagnostic is longer than the maximum size of
the command interface, it must be read with several adjacent requests.
The byte 5 ('index') declares the start index in the array of diagnostic data. If this
start index is 0, the whole diagnostic is fetched from the monitor and stored to an
internal buffer. Otherwise, the AS-i Master will respond out of the internal buffer.
Thus, even though several requests are necessary to read the whole buffer, data
integrity is maintained.
byte
1
2
3
4
5
1.
L=1 long diagnostic for advanced monitor.
2.
U=1 unsorted diagnostic (all devices).
byte
1
2
3
4
...
n
The diagnostic array is set up as follows:
byte
0
1
2
3
4
5
6
7
6
5
2
2
2
T
1
2
L
U
7
6
5
2
2
2
T
Safety Monitor Diagnostic Array
"basic function range" and "sorted by OSSD"
7
6
5
2
2
2
number of devices not green, OSSD1
number of devices not green, OSSD2
Request
4
3
2
2
7E
16
02
16
slave address
index
Response
4
3
2
2
7E
16
result
diagnostic byte #index+0
diagnostic byte #index+1
...
diagnostic byte #index+n-3
4
3
2
2
00
16
state of monitor
state of OSSD 1
state of OSSD 2
device index 32, OSSD 1
2
1
2
2
2
circuit
Tab. 4-222.
2
1
2
2
2
Tab. 4-223.
2
1
2
2
2
Tab. 4-224.
0
0
0
117