5.5.13 2 DI/DO I/O Modules with 1 Bit Diagnostics per Channel

Index
'0000.0000'
'0000.0001'
'0010.0000'
'0010.0001'
'0010.0010' *) Input data channel 3
'0010.0011' *) Input data channel 4
'0100.0000'
'0100.0001'
'1010.0000'
'1100.0000'
*)

5.5.14 Supply Module with Diagnostics

Index
'0000.0000'
'0010.0000' *) Input data channel 1
'0010.0001' *) Input data channel 2
'1010.0000' *) Input data module
*)
WAGO-I/O-SYSTEM 750
Bus System
Meaning
Diagnostics data channel 1
Diagnostics data channel 2
Input data channel 1
Input data channel 2
Output data channel 1
Output data channel 2
Input data module
Output data module
These indices are only available when the mapping of diagnostics data into the input
process image is enabled
Meaning
Diagnostics data
These indices are only available when the mapping of diagnostics data into the input
process image is enabled
Acyclic Communication According to DP/V1
Service Primitives / Data Length
MSAC1/2_Read / 2 byte
MSAC1/2_Read / 2 byte
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read,
MSAC1/2_Write / 1 bit (byte)
MSAC1/2_Read,
MSAC1/2_Write / 1 bit (byte)
MSAC1/2_Read / 1 byte
MSAC1/2_Read,
MSAC1/2_Write / 1 byte
Service Primitives / Data Length
MSAC1/2_Read / 2 byte
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read / 1 bit (byte)
MSAC1/2_Read / 1 byte
I/O Modules
• 213