82 •
Programmable Field Bus Controller 750-833
Configuration
Modules are compiled in the table to make things simpler.
Module
Module
*-Module
RA module
PFC module
3.6.4.1

Bus Controller Modules

3.6.4.2

I/O Modules

Note
You can find a list of all I/O modules with all possible identification bytes in
chapter 5.3 "PROFIBUS Identification Bytes of I/O Modules ".
Meaning
Configuration for digital I/O modules:
A new byte is generated in the
respective process image. The binary
information of the I/O modules is
mapped on the least significant bit of
the byte.
Configuration for analog I/O modules:
Only the user data required for
operating the I/O module are mapped in
the appropriate process image area
(input process image and/or output
process image).
Configuration for digital I/O modules.
A module opened byte is fulfilled with
binary information of the I/O module.
Configuration of complex, in particular
analog I/O modules. Input and output
information inclusive CONTROL and
STATUS byte is mapped in the
respective process image area. This
way, the register structure of the
respective I/O modules can be accessed
when parameterization is done via
cyclic process data exchange.
Allocation of the individual I/O module
to the process image of the internal
PLC. The process data is exclusively
available for the PFC user program.
Order No.
Description
750-833
no process data channel
750-833
2 byte process data channel
750-833
4 byte process data channel
Example
750-400 2 DI/24 V DC/3.0 ms
750-461 2 AI/RTD
750-550 2 AO/0-10 V
*750-400 2 DI/24 V DC/3.0 ms
750-461 2 AI/RTD RA
750-550 2 AO/0-10 V RA
PFC 750-400 2 DI/24 V DC/3.0
ms
Module
0x00
0xB1
0xB3
WAGO-I/O-SYSTEM 750