64
Commissioning
This area provides information about occurring diagnostics. If you have activated
diagnostics in the Channel settings menu item and a diagnostic occurs, the
diagnostic is displayed in the status messages window. These status messages are
determined from the status bytes of the individual channels.
Click the button to expand the Status Messages window at the bottom of the
parameterization dialog to display the status messages.

Figure 28: Expanding the Status Messages Window

The following status messages with corresponding additional information are
displayed:
Table 32: Status Messages – Possible Status Messages with Additional Information
Status message
Measurement range overflow
Measurement range underflow
User-defined limiting value
overrange
User-defined limiting value
underrange
Short circuit
Wire break
Channel deactivated
Measured values in permissible
range
The status messages are displayed with assignment of the relevant I/O module
channels.

Figure 29: Status Messages in the Application Window of the Parameterization Dialog

Click the [Delete] button to clear the status message history. The history is
automatically cleared if you interrupt the connection to the I/O module or close
the parameterization dialog.
750-496 8AI 0/4-20mA S.E.
Error type
Channel
Warning
x
Warning
x
Warning
x
Warning
x
Error
x
Information
x
Error
x
Information
x
Information
x
Information
x
WAGO-I/O-SYSTEM 750
Status byte
0x42
0x41
0x04
0x08
0x50
0x00
0x60
0x00
0x00
0x00
Manual
Version 1.2.0