3.2.5 Station Address

The station address is determined via two decimal rotary switches on the bus
controller.
ADDRESS
Fig. 3.2.5-5: Creating the station address
The switch „x1" determines the unit position of the address. The switch „x10"
determines the tens position of the address. Valid station addresses lie between
1 and 99.
The station address is taken over by the field bus coupler after switching on
the device (initialization phase). Adjustments to the switch during operation
have no effect.
Note
After Power-On the station address 0 causes the run-up of the controller and
start of the PFC functions, without the field bus being active.
Using this function, an Stand Alone, smallest scale control can be realized
using the WAGO-I/O-SYSTEM 750
Any station address may be used from SW 03. The user determines whether
the controller may start up with the default configuration using a functional
building block.