Commissioning Suggestions - gefran SIEIDrive LIFT AGy -L Instruction Manual

Lift vector ac drives
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 47
Before changing the parameter settings make sure that the starting values are default values.
Change the parameters one at the time; if the change on any parameter is not effective, restore the param-
Attention
eter initial value before changing another one.
In order to avoid problems linked to running comfort, it is advisable to perform a preliminary control of the motor
parameters.
Check in the STARTUP menu that the value set in the following parameters corresponds to the motor nameplate data:
S.100 Base voltage
S.101 Base frequency
S.150 Motor rated curr
S.151 Motor pole pairs
S.152 Motor power fact
In order to avoid too high settings of the acceleration and deceleration values (jerk), make sure that the slowing-down
distances correspond to those listed in the table:
Suggested slowing-down distances
Plant rated speed
Suggested slowing-down distance
Such distances grant a high running comfort with the factory set jerk values.
The default speed levels can be selected on the terminals 25, 7 and 6. It is advisable to use the frequencies as
follows:
S.200 Frequency ref 0
S.201 Frequency ref 1
Other speeds (maintenance, rephasing procedure etc.) can be selected as per table 7.2.
In the open loop plants (without encoder), the boost can be increased if the lift car tends to rotate in the opposite
direction during the starting phase or if it can not start in spite the running speed has been set (S.300 Manual boost,
default = 3). The boost should be gradually increased by 1% at the time. Too high values cause the intervention of the
current limit alarm.
68

6 - Commissioning suggestions

Inverter maximum output voltage (Vrms).
Motor base frequency (Hz).
Motor rated current (Arms).
Number of motor polepairs.
(cos phi) Motor input power factor with rated current and voltage.
(m/s)
(mm)
Slow speed: it is the floor reaching speed (frequency)
High speed: it is the rated speed (frequency) required by the motor for that specific
plant.
0.8
1.0
1.2
1000
1300
1700
1.4
1.6
1.8
2000
2300
2600
2
3000
tab 060-g
AGy -L