WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Pos : 101 /Alle Serien (Allgemei ne M odul e)/Ü bersc hriften/Ebene 1/Di agnose - Übersc hrift 1 @ 4\mod_1240831069471_21.doc x @ 31372 @ 1 @ 1
9

Diagnostics

Pos : 102 /Serie 750 (WAGO-I/O-SYST EM)/Diagnos e/Bus klemmen/Diagnos e 750- 0494, - 0495 @ 13\mod_1348662372924_21.doc x @ 103550 @ @ 1
LED A indicates the operating status, LEDs B ... H indicate possible errors.
The meaning of these indications is as follows:

Table 22: Diagnostics

LED
A
B
C
D
E
F
G
H
Pos : 103 /Dokumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.0
State
Message
No operational readiness or
the internal data bus communication is interrupted.
Off
Note: If the watchdog was disabled, the LED is
always green. See section "Commissioning" >
"Configuration with WAGO-I/O-CHECK".
Operational readiness and correct internal data bus
Green
communication
Off
No error
General error message for L1:
Red
Under-/overvoltage or overcurrent
Off
No error
General error message: Clipping of a current
Red
measuring path IL1, IL2 or IL3
Off
No error
High measuring error, caused by undershooting the
Red
min. voltage at L1, L2 or L3
Off
No error
General error message for L2:
Red
Under-/overvoltage or overcurrent
Off
No error
General error message for L3:
Red
Under-/overvoltage or overcurrent
Off
No error
General error message: Clipping of a voltage
Red
measuring path L1, L2 or L3
Off
No error
Yellow
Error of the phase sequence L1-L2-L3
Diagnostics
99