WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Pos : 110 /Serie 750 (WAGO-I/O-SYST EM)/In Betri eb nehmen/Par ametrieren über R egister kommuni kati on/Registerbeleg ung und Parameterbel. 750-494 @ 15\mod_1364991593084_21.doc x @ 116384 @ 22 @ 1
10.3

Register Assignment

The tables below show the assignments and factory settings for the registers
written during configuration and during operation. All registers have a size of two
bytes.

Table 24: Register 4

Command Interface Request
High byte
Sequence number (Session ID)
Low byte
Request
0x04
0x37
0x38
0x39
0x3A
0x3B
0x3C
0x3D
0x3E
0x3F
0x40
0x41
0x42
0x43
0x44
0x45
0x91
0x92
0x93
0x94
0x95
0x96
0x97
0x98
0x99
0x9A
0x9B
0x9C
0x9D
0xA0
0xA1
0xA2
0xA3
0xA4
Manual
Version 1.2.0
Register 4 – Command interface request
Function
Reset register and calibration data to factory default settings
Preset apparent energy delivery phase L1
Preset apparent energy delivery phase L2
Preset apparent energy delivery phase L3
Preset active energy acquisition phase L1
Preset active energy delivery phase 1
Preset active energy acquisition phase L2
Preset active energy delivery phase L2
Preset active energy acquisition phase L3
Preset active energy delivery phase L3
Preset reactive energy inductive phase L1
Preset reactive energy capacitive phase L1
Preset reactive energy inductive phase L2
Preset reactive energy capacitive phase L2
Preset reactive energy inductive phase L3
Preset reactive energy capacitive phase L3
Save energy consumption early
Delete all minimum and maximum values
Delete minimum RMS current
Delete maximum RMS current
Delete minimum RMS voltage
Delete maximum RMS voltage
Delete minimum power
Delete maximum power
Initialize all energy meters to 0
Delete minimum frequency
Delete maximum frequency
Reset registers and parameters to factory settings
Reset calibration data to factory settings
Start mode for manufacturer calibration for AC operation
Start mode for manufacturer calibration for DC operation
Start mode for user calibration for AC operation
Start mode for user calibration for DC operation
Start mode for measuring operation (halts calibration mode)
Data type
Access
UINT
R/W
Appendix
107
Factory setting
0x0000