Collections Of Measured Values; Collection 007 - Dc Measured Values; Collection 009 - Ac Measured Values; Table 17: Measured Values Of Collection 007 In The Process Image (Pi) - WAGO 750-494 Series Manual

3-phase power measurement module
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
5.5

Collections of Measured Values

5.5.1
Collection 007 – DC Measured Values
Wait to the end of build-up time!
The selected measured values of the collection are stable after approx. 1400 ms!

Table 17: Measured Values of Collection 007 in the Process Image (PI)

MET_ID Measured Value
Current
001
002
003
Voltage
004
005
006
Power
007
008
009
5.5.2
Collection 009 – AC Measured Values
Wait to the end of build-up time!
The selected measured values of the collection are stable after approx. 1400 ms!
Manual
Version 1.2.0
DC current L1
DC current L2
DC current L3
DC voltage L1-N
DC voltage L2-N
DC voltage L3-N
Power (DC current) L1
Power (DC current) L2
Power (DC current) L3
Scaling Factor PI
Data
Type
1A-
PI
Variants
Variants
UInt32
0.0001A
UInt32
0.0001A
UInt32
0.0001A
UInt32
0.01V
UInt32
0.01V
UInt32
0.01V
UInt32
0.01W
UInt32
0.01W
UInt32
0.01W
Process Image
55
Update
Rate PI
5A-
[ms]
0.0005A
40
0.0005A
40
0.0005A
40
0.01V
40
0.01V
40
0.01V
40
0.05W
40
0.05W
40
0.05W
40