Factory Settings" Tab; Figure 26: "Factory Settings" Tab - WAGO 750-494 Series Manual

3-phase power measurement module
Table of Contents

Advertisement

88
Commissioning
8.1.5

"Factory Settings" Tab

After entering a password (see "Energy" tab above), you can reset all parameters
of the I/O module to their factory settings on the "Factory Settings" tab.
List of factory settings
A list of factory settings may be found in section "Appendix".
Use I/O Module Settings [Restore] to reset the I/O module settings only.
Calibration data remains unchanged.
Use Calibration Data [Restore] to reset the calibration data only. The I/O module
settings remain unchanged.
Use Total [Restore] to reset all I/O module settings and calibration data.
These actions are carried out immediately and cannot be undone. Therefore, the
[Save] button is disabled at the bottom of the window.

Figure 26: "Factory Settings" Tab

WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0