Connect Devices
connected measuring instruments. FS shall be max. 10 for the 1 A module resp.
max. 5 for the 5 A module.
Note the max. continuous measuring current of 1 A resp. 5 A!
The max. continuous measuring current of the module is 1 A resp. 5 A. If the used
transformers allow greater secondary currents than 1 A resp. 5 A install additional
transformers with an appropriate transforming ratio!
7.3.2.4

Protection against Shock Hazard Voltages

No hazardous voltage is produced when the 3-phase power measurement module
is used as specified, with appropriate current transformers. Secondary voltage is
only a few Volts. Nevertheless, the following faults can result in high voltage
levels:
Open current path for one or more transformers
Disconnected/cut N conductor at the voltage measuring end of the 3-phase
power measurement module
General insulation faults
Install protection against electric shock!
All wiring for the measurement system shall be equipped with protection against
shock hazard voltages along with the corresponding safety signs!
The 3-phase power measurement module permits a maximum voltage of 480 V
for normal operating conditions. The voltages at the voltage inputs shall not
exceed 480 V. For higher voltages use a transformer stage. This one however,
shall not produce a phase angle shift (Yy0)!
The 3-phase power measurement module is equipped with a protective impedance
of 1072 kΩ at the voltage measurement end. If the N conductor is not connected,
and only one of the three voltage measuring terminals is under power, a voltage of
230 VAC to ground is yielded in a 3-phase system with a phase-to-phase voltage
of 400 VAC. This voltage is also present at the current measuring end and can be
measured using a multimeter with 10 MΩ input resistance. This does not represent
an insulation fault.
WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Manual
Version 1.2.0