110
Appendix
Table 30: Register 38
Undervoltage threshold phase L3,
0:
≥1:
Table 31: Register 39
Divisor for the current transformer ratio,
Activation via Register 32, Bit 12 required
0:
≥1:
Table 32: Register 40
Divisor for the current transformer ratio,
Activation via Register 32, Bit 13 required
0:
≥1:
Table 33: Register 41
Divisor for the current transformer ratio,
Activation via Register 32, Bit 14 required
0:
≥1:
Register 38 – Undervoltage threshold phase L3
Function
Resolution: 0.1 V
Checking of undervoltage threshold is deactivated.
Value for undervoltage threshold.
Register 39 – Current transformer ratio phase L1
Function
phase L1,
-not permitted-
Value for the current transformer ratio divisor D-CTR.
Register 40 – Current transformer ratio phase L2
Function
phase L2,
-not permitted-
Value for the current transformer ratio divisor D-CTR.
Register 41 – Current transformer ratio phase L3
Function
phase L3,
-not permitted-
Value for the current transformer ratio divisor D-CTR.
WAGO-I/O-SYSTEM 750
750-494 3-Phase Power Measurement Module
Data type
Access
UINT
R/W
Data type
Access
UINT
R/W
Data type
Access
UINT
R/W
Data type
Access
UINT
R/W
Factory setting
0 x 0000, 0 V
Factory setting
0x0001
Factory setting
0x0001
Factory setting
0x0001