3-Phase Power Measurement Module - WAGO 750-494 Series Manual

3-phase power measurement module
Table of Contents

Advertisement

44
Process Image
OVER_2
OVER_3
OVER_4
STAT_SEL
Expanded status word 1
(Bit 7)
STAT7 STAT6
STAT7
STAT6
STAT5
Range limiting for process value 2:
0 = Ok
1 = The measured value shown in process value 2
is situated outside the defined value range.
Range limiting for process value 3:
0 = Ok
1 = The measured value shown in process value 3
is situated outside the defined value range.
Range limiting for process value 4:
0 = Ok
1 = The measured value shown in process value 4
is situated outside the defined value range.
Confirmation for the status query requested in the output data
– Status active for:
0 = Status Phase L1
1 = Status Phase L2
2 = Status Phase L3
3 = Status I/O module
(Bit 6)
(Bit 5)
STAT5
STAT_SEL = Status Lx = L1 / L2 / L3:
- Threshold value Undervoltage Lx:
0 = Threshold not reached
1 = Threshold reached or exceeded
STAT_SEL = Status I/O module:
No significance
STAT_SEL = Status Lx = L1 / L2 / L3:
- Threshold value Overvoltage Lx:
0 = Threshold not reached
1 = Threshold reached or exceeded
STAT_SEL = Status I/O module:
Rotating Field Indicator
0 = Rotary field correct L1-L2-L3, clockwise
1 = Rotary field not correct, counter-clockwise
STAT_SEL = Status Lx = L1 / L2 / L3:
- Threshold value Overcurrent Lx:
0 = Threshold not reached
1 = Threshold reached or exceeded
STAT_SEL = Status I/O module:
No significance

750-494 3-Phase Power Measurement Module

Byte 2
(Bit 4)
(Bit 3)
STAT4
STAT3
WAGO-I/O-SYSTEM 750
(Bit 2)
(Bit 1)
(Bit 0)
STAT2
STAT1
Manual
Version 1.2.0
-

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-494/025-001750-494/025-000750-494/000-001