Festo CPV -VI Series Manual page 76

Compact performance cpv valve terminal, pneumatics
Hide thumbs Also See for CPV -VI Series:
Table of Contents

Advertisement

4. Commissioning
PLEASE NOTE
• • Use a blunt pointed object for actuating the
• • Actuate the manual override with max. 30 N.
You thereby avoid functional interference or damage
to the manual override.
Testing
Proceed as follows:
• • Switch on the compressed air supply.
• • Check the functioning and mode of operation of each
• • When the test is finished, switch off the compressed
Actuate the manual override with automatic reset
(pushing)
4-8
manual override with automatic reset.
individual valve cylinder combination with the manual
override as shown in the diagrams below.
air supply again.
Carefully press the
plunger of the manual
override as far as it
will go.
Hold the plunger of
the manual override
pressed down.
Release plunger.
Spring resets the
plunger to basic
position.
Reaction of valve
The valve:
– switches.
– remains switched
– returns to basic position
(not with 5/2-way double
solenoid valve, Ident.
code J)
CPV... 9811d