Page 1
Compact Performance Brief description CPV valve terminal with direct connection type CPV...-DI02 PROFIBUS-DP – English 8080225 2017-11a [8080227]...
Page 2
Translation of the original instructions Documentation on the product For all available product documentation è www.festo.com/pk PROFIBUS®, PROFIBUS-DP® are registered trademarks of PROFIBUS International (P.I.) Copyright: Festo SE & Co. Ruiter Straße 82 73734 Esslingen Germany Internet: http://www.festo.com E-Mail: service_international@festo.com Reproduction, distribution or sale of this document or communication of its contents to others without express authorization is prohibited.
Page 3
IEC/DIN EN 60204-1. Observe also the general requirements for PELV power circuits as per IEC/DIN EN 60204-1. S Connect an earth conductor of sufficient diameter to the connection marked with the earth symbol. Festo CPV...-GE-DI02-8 2017-11a English...
M12 connection Pin no. 1. 24 V DC operating voltage for the electronics and inputs 2. 24 V DC load voltage for valves 3. 0 V 4. Earth connection On the CPI extension connection of connected modules Festo CPV...-GE-DI02-8 2017-11a English...
Page 5
Pin assignment of the field bus connection (Sub-D-9 socket) PROFIBUS-DP Pin 3 (B) RxD/TxD-P Pin 8 (A) RxD/TxD-N In brackets: Connection on the Festo Sub-D plug type FBS-SUB-9-GS-DP-B Detailed information can be found in the manual P.BE-CP-DI02-... Festo CPV...-GE-DI02-8 2017-11a English...
Page 6
(see section 7). 5. Refit the switch cover. 6. If the CPI system is the first or last slave in a field bus segment, the terminating resistor in the Festo Sub-D plug must be activated. Warning S Check the measures for putting the system into a safe state in the event of an EMERGENCY STOP.
Permitted station numbers are: 1; …; 125 Coded entry Example: Station number: 38 2 + 4 + 32 = 4.2 Set device-related diagnosis The device-related diagnosis can be activated/deactivated with switch element 8 of the DIL switch. Diagnosis ON Diagnosis OFF Festo CPV...-GE-DI02-8 2017-11a English...
Page 8
CP extension string each occupy 8, 16, ... input or output addresses depending on the design. Note the relevant documentation for the module. Detailed specifications and examples of addressing the CP system can be found in the manual P.BE-CP-DI02-... Festo CPV...-GE-DI02-8 2017-11a English...
Field bus connection not OK lights up: Hardware fault (servicing required) Other faults flashes fast: Configuration fault in CP string flashes slowly: Module in the CP string has diagnostic case lights up: Module failure in the CP string Festo CPV...-GE-DI02-8 2017-11a English...
Page 10
With a new or modified string assignment the LED P flashes. 2. Press the SAVE button for at least 1 s. The LED goes out P. 3. Check the address assignments of your CPI system before starting user programs. Festo CPV...-GE-DI02-8 2017-11a English...
10 m between the CPV Direct and the last CPI/CP module or valve terminal – Modules max. 4 modules with together max. 32 inputs and 32 outputs on the CP string Further rules in the manual P.BE-CP-DI02-... Festo CPV...-GE-DI02-8 2017-11a English...
Page 12
CP solenoid valves; see manual “CP pneumatics” Residual ripple 4 Vpp (within tolerance) Electrical isolation bus interface opto-decoupled Valves see Pneumatics manual P.BE-CPV-... Detailed information on the CPV Direct can be found in the manual P.BE-CP-DI02-... Festo CPV...-GE-DI02-8 2017-11a English...