Ac Power Cables; Power Consumption; Dc Supplies Required For Drive Expansion Module - Example; Power Cable Descriptions - Oracle StorageTek SL3000 Manual

Modular library system
Hide thumbs Also See for StorageTek SL3000:
Table of Contents

Advertisement

Power Configurations
Table 1–9
Configuration Option
N+1 (240VAC PDU)
2N (240VAC PDU)
2N+1 (240VAC PDU)
The number of drive DC supplies that must be ordered depends on the power
configuration selected. For instance, if the example library had a 2N+1 configuration, it
would require an order of six additional drive DC power supplies (four supplies for
the Base module and two supplies for the DEM). The 2N+1 also requires an additional
DC supply for the robotics and an additional ECM 200W cPCI power supply. The ECM
power supply is different than the tape drive and robot power supplies listed in this
example. For ordering information, see

AC Power Cables

The following table lists the cables required for each power configuration. You must
order one power cord per PDU installed:
N+1 — order one power cord for the Base module and an additional power cord
for the DEM (if installed)
2N or 2N+1 — two power cords for the Base module and two additional power
cords for the DEM (if installed)
Table 1–10
Power Source
120 VAC/20A
240 VAC/30A
240 VAC/30A

Power Consumption

For environmental or economical reasons, you might want to determine the total
power consumption (watts), CO
for the SL3000 library and tape drives. The table below provides power consumption
in watts.
Table 1–11
Components
Base Library (required)
Includes: 1 ECM, 1 robot, and 1 CAP
Redundant Electronics (optional)
Redundant Robotics (optional)
Operator Panel (optional)
Additional CAPs (optional)
Access Expansion Module (optional)
1-14 StorageTek SL3000 Library Guide

DC Supplies Required for Drive Expansion Module - Example

DC Supplies
Required
2
2
4

Power Cable Descriptions

Circuit
Description
Breaker
US/Japan
20A
US
30A
International 30A
emission values, and British Thermal Units (Btu/hr)
2

Power Consumption Values

DC Supplies to Order
(= Required - 2)
0
0
2
"DC Power Supplies"
on page 1-28.
Wall
Library
Connector
Connector
L5-20P
L5-20R
L6-30P
L6-30R
330P6W
L6-30R
Quantity
Idle Watts
1
156
1
100
1
28
1
29
Each
10
Each
8
Power Cord
Length/Type
3.7 m (12 ft) 12 AWG
3.7 m (12 ft) 12 AWG
4 m (13 ft) HAR
Max Watts
197
100
55
37
14
30

Advertisement

Table of Contents
loading