P12 - Digital Inputs

This menu is divided into 20 sections. These refer to 8 possible digital inputs INP1...INP8
that can be managed directly by the ATC6500, and a further 12 inputs that can be managed
by the ATC6500 via the expansion modules.
P12
Designation on ATC
display
P12.n.01 INPUT FUNCTION
P12.n.02 CHANNEL NO.
P12.n.03
CONTACT TYPE
P12.n.04 DELAY ON
P12.n.05
DELAY OFF
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Description
TEST duration
– Duration of the periodic test in minutes.
Automatic TEST with load transfer
– Load management during performance of the periodic test:
OFF = The load is not transferred.
Load = Enables load transfer from the network to the generator.
Dummy load = Load simulation is activated; the system load is not
transferred.
Description
Function of the input INPn
– Selects the function of the selected input (see
table "Functions of the programmable inputs" in
chapter Digital inputs INPx (Page 145))
Function index (x)
- Index that is possibly assigned to the function
programmed in the previous parameter. Example: If
the input function is set to Cxx Commands menu
execution, and this input is to perform command
C07 in the Commands menu, then P12.n.02 must
be set to the value 7.
Contact type
– Select the contact type: NO (normally open) or
NC (normally closed)
Closing delay
– Contact closing delay for selected input.
Opening delay
– Contact opening delay for selected input
Parameterization
9.4 Parameters
Unit
De-
Range
fault
min
10
1-600
OFF
OFF
Load
Dummy
load
Unit
Default
Range
(misc.)
(See Table:
Functions of
the inputs
(Page 145))
OFF
OFF / 1-99
NO
NO/NC
s
0.05
0.00-600.00
s
0.05
0.00-600.00
179