Siemens SENTRON ATC6500 Manual page 209

Transfer switching equipment and load transfer switches 3kc transfer control device
Table of Contents

Advertisement

Step 4: Set the value 8
Master
01
ATC
Step 5: Save and reboot
Master
ATC
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
Function
Address
Value
Number of registers
Number of bytes
10
50
03
Function
Address
Value
01
10
Function
Address
Value
01
06
No response
10.7 Changing parameters by means of MODBUS
= 16 (10H)
= 5004H (5004H - 0001H = 5003H)
= 1 (01H)
= 1 (01H)
= 8 (0008H)
00
01
02
= 16 (10H)
= 5004H (5004H - 0001H = 5003H)
= 2 (02H)
50
03
= 6 (06H)
= 2F03H (2F03H - 0001H = 2F02H)
= 5 (04H)
2F
02
MODBUS communication
00
08
CA
00
01
00
05
F7
A0
E0
C9
E0
DD
207